products   references   latest news   distributors   contacts

home | references | Airport Schwechat


 
projects in aviation fuel handling worldwide References
Airport Schwechat, Wien, Austria

 



enlarge

filtration fuel farm, equipped with
WARNER LEWIS filter separators
according to API 1581 3rd Edition.
Technical data:
  1. 4 off model no. V-3644 WARNER LEWIS filter separator according to API Specification 1581, Group II, Class B, 3rd Edition May 1989
  • Max. flow rate: 323 m³/h jet fuel
  • Design pressure: 16 bar
  • Design temperature: -10 / +50 °C
  • Material: Carbon steel
  • Equipped with:
    • 1st stage: 11 off I-64487TB Velcon coalescer elements
    • 2nd stage: 5 off SO-636V Velcon separator elements
  1. 1 off model no. V-2444 WARNER LEWIS filter separator according to API Specification 1581, Group II, Class B, 3rd Edition May 1989
  • Max. flow rate: 124 m³/h jet fuel
  • Design pressure: 8 bar
  • Design temperature: -10 / +50 °C
  • Material: Carbon steel
  • Equipped with:
    • 1st stage: 5 off I-64487TB Velcon coalescer elements
    • 2nd stage: 2 off SO-640PV Velcon separator elements



enlarge

Front view of filtration fuel farm